Mixing Valve

Installation of mixing valve
Balancing Vessel
(Mixing tank)
When two different zones are used with different temperature, adjust the temperature of discharge water to high
temperature water and control the amount of bypass to provide low temperature water by applying the mixing valve and
temperature sensor of the mixing valve (TW4) .
1 . Select a mixing valve from the manufacturers as below (recommended) and install it at the enterance of the zone .
2 . Install the supplied temperature sensor (TW4) on the rear part of the mixing valve .
3 . Since running time varies depending on the manufacturer, set the FSV (default 90 sec . ) by referring to the FSV value
below .
Maker
Model code
Running time
FSV(#4046) setting
❋ ❋ The table above is for your reference . It can be changed without advanced notice .
4 . Set the FSV value by referring to the table below depending on installation environment .
Function
Target temperature difference
(Heating) (TW2-TW4)
Target temperature difference
Mixing valve
(Cooling) (TW4-TW2)
Interval of valve control
Running time (10 second unit)
❋ ❋ The additional pump and mixing valve should be purchased separately . TW4 sensor is included in the product
accessories .
❋ ❋ TW2 : Water temp . sensor 2
• When the thermostat control is set as 'Use' , the mixing valve can be used for Zone 1 and Zone 2 . (When both FSV
#2091 and #2092 are set as 1)
CAUTION
EHS MONO Kit-EU_IM_05388A-00_EN.indd 39
TW4
3 Way Valve
R3020-6P3-S2
Actuator
LR230A(-S)
Details
Code
Use or not
4041
4042
4043
Control factor
4044
4045
4046
Radiator
Under Floor
BELIMO
SIEMENS
VXP45 . 2 0-4 (kvs 4)
SSB31
90 sec .
150 sec .
9
15
Unit
Default
-
0(No)
°C
10
°C
10
-
2
Min .
2
(x10) sec
9
HONEYWELL
V5011E1213
ML6420A3015
60 sec .
6
Min.
Max.
0
1(Yes)
5
15
5
15
1
5
1
30
6
24
39