Humidity; Vibration And Shock - Omron NYB17-11 User Manual

Industrial box pc ny-series
Table of Contents

Advertisement

OMRON
Fan
product
OMRON
product
Forced Air Circulation
 Room Cooling
Cool the entire room where the control panel is located.
Low Temperatures
The Box PC may not start normally if the temperature is below 0°C when the power is turned ON.
Maintain an air temperature of at least 5°C inside the panel, by implementing measures such as instal-
ling a low-capacity space heater in the panel.
Alternatively, leave the Box PC power ON to keep the Box PC warm.
5-3-4

Humidity

Rapid temperature changes can cause condensation to occur, resulting in malfunctioning due to short-
circuiting.
When there is a possibility of this occurring, take measures against condensation, such as leaving the
Box PC power ON at night or installing a heater in the control panel to keep it warmer.
Power ON
5-3-5

Vibration and Shock

The Box PC is tested for conformity with the sine wave vibration test method (IEC 60068-2-6) and the
shock test method (IEC 60068-2-27) of the Environmental Testing for Electrotechnical Products. It is
NY-series Industrial Box PC User's Manual (W553)
Cooler
Control panel
Room Cooling
Control panel
Moisture
absorber
OMRON
product
Examples of Measures against Condensation
Heater
5 Installation
5
5 - 19

Advertisement

Table of Contents
loading

Table of Contents