5 Installation
Power Supply (S8VK)
AC (L)
AC (N)
4
Power ON the Box PC.
5
Configure the UPS.
(1) Connect the USB cable supplied with the UPS to the USB connector of the UPS and to the
USB connector of the Box PC.
(2) Configure the UPS using the UPS Settings Utility.
Refer to UPS Setting Utility Instruction Manual for S8BA/BU-2RWL for details.
(3) Remove the USB cable between the UPS and the Box PC
6
Configure the Box PC to auto-start after power loss within the BIOS settings.
• Refer to A-1-1 BIOS Overview on page A - 2 for details on BIOS changes.
• Refer to A-1-5 BIOS - Boot on page A - 9 for power loss BIOS details.
7
Create a software program that monitors the UPS Mode Input and initiates Power OFF of the
Box PC when the UPS Mode Input becomes active.
If the Box PC has a Windows operating system then use the Industrial PC System API to cre-
ate the software program.
Refer to NY-series Software Development Kit User's Manual for API details.
8
Install the created software program.
9
Test the created software program and ensure it functions correctly.
10
Simulate a power interruption and confirm a correct shutdown of the Box PC.
• Start the Box PC
• Start applications
• Create a power interruption
• Monitor the shutdown sequence and confirm a correct shutdown sequence
The UPS is connected and configured.
The Box PC will shut down properly in case of a power supply interruption and restart automatically
when the power is restored.
5 - 56
UPS (S8BA)
24 VDC
Input
24 VDC
0 VDC
Output
24 VDC
0 VDC
COM
4
BU
1
6
BS
Contact
NY-series Industrial Box PC User's Manual (W553)
IPC Product
6
UPS Mode Input
5
UPS Mode Input
2
Power Status Output
1
Power Status Output
I/O