Single-phase 200V power supply

Model FR-D720S- K
Model FR-D720S- -NA
Model FR-D720S- -EC
Model FR-D720S- K-CHT
Applicable motor capacity (kW)
Rated capacity (kVA)
∗2
Rated current (A)
Overload current rating
∗3
Voltage
∗4
Rated input AC voltage/frequency
Permissible AC voltage fluctuation
Permissible frequency fluctuation
Power supply capacity (kVA)
Protective structure (JEM1030)
Cooling system
Approximate mass (kg)

Single-phase 100V power supply

Model FR-D710W- K
Model FR-D710W- -NA
Applicable motor capacity (kW)
Rated capacity (kVA)
∗2
Rated current (A)
Overload current rating
∗3
Voltage
Rated input AC voltage/frequency
Permissible AC voltage fluctuation
Permissible frequency fluctuation
Power supply capacity (kVA)
Protective structure (JEM1030)
Cooling system
Approximate mass (kg)
∗1
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
∗2
The rated output capacity indicated assumes that the output voltage is 230V.
∗3
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for
the inverter and motor to return to or below the temperatures under 100% load. If the automatic restart after instantaneous power failure function (Pr. 57) or
power failure stop function (Pr. 261) is set and power supply voltage is low while load becomes bigger, the bus voltage decreases to power failure detection
level and load of 100% or more may not be available.
∗4
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,
the pulse voltage value of the inverter output side voltage remains unchanged at about
∗5
The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
∗6
For single-phase 100V power input model, the maximum output voltage is twice the amount of the power supply voltage and cannot be exceeded.
∗7
In a single-phase 100V power input model, the output voltage may fall down when the load is heavy, and larger output current may flow compared to a three-
phase input model. Use the motor with less load so that the output current is within the rated motor current range.
0.1
0.2
008
014
008
014
0.1
0.2
0.1
0.2
∗1
0.3
0.6
0.8
1.4
150% 60s, 200% 0.5s (inverse-time characteristics)
Three-phase 200 to 240V
Single-phase 200 to 240V 50Hz/60Hz
170 to 264V 50Hz/60Hz
0.5
0.9
∗5
Self-cooling
0.5
0.5
0.1
0.2
008
014
0.1
0.2
∗1
0.3
0.6
0.8
1.4
150% 60s, 200% 0.5s
(inverse-time characteristics)
Three-phase 200 to 230V
Single-phase 100 to 115V 50Hz/60Hz
90 to 132V 50Hz/60Hz
±5%
0.5
0.9
∗5
Enclosed type (IP20).
Self-cooling
0.6
0.7
0.4
0.75
1.5
025
042
070
025
042
070
0.4
0.75
1.5
0.4
0.75
1.5
1.0
1.7
2.8
2.5
4.2
7.0
±5%
1.5
2.3
4.0
Enclosed type (IP20).
Forced air cooling
0.9
1.1
1.5
0.4
0.75
025
042
0.4
0.75
1.0
1.7
2.5
4.2
∗6, ∗7
1.5
2.5
0.9
1.4
that of the power supply.
2
2.2
100
100
2.2
2.2
4.0
10.0
5.2
2.0
6