YASKAWA Z1000 Technical Manual page 22

Bypass option profinet
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

6 Related Bypass Parameters
No.
(Addr.
Name
Hex)
Z4-16
Communication Loss Timeout Control connection timeout value for detection of communication loss.
(870F)
Z4-23 to
Dynamic Output Assembly
Z4-27
Parameters DOA116 1 to
(8716 to
DOA116 5
871A)
Z4-33 to
Dynamic Input Assembly
Z4-37
Parameters DIA166 1 to
(8720 to
DIA166 5
8724)
<1> When set to 3, the drive will continue to operate when a fault is detected. Take safety measures, such as installing an emergency stop switch.
<2> Available in bypass controller software versions VST800400 and later.
No.
Name
U6-80 to
Online IP Address
U6-83
U6-84 to
Online Subnet
U6-87
U6-88 to
Online Gateway
U6-91
U6-92
Online Speed
U6-93
Online Duplex
U6-94
Port 2 Speed
U6-95
Port 2 Duplex
U6-97
Option Software Version
U6-98
First Fault
U6-99
Current Fault
22
'Parameters used in Dynamic Output PZD
'Parameters used in Dynamic Input PZD
Table 5 Option Monitors
IP Address currently available; U6-80 is the most significant octet
Subnet currently available; U6-84 is the most significant octet
Gateway currently available; U6-88 is the most significant octet
Link Speed
Duplex Setting
Port 2 Link Speed
Port 2 Duplex Setting
Option Software Version
First Option Fault
Current Option Fault
YASKAWA SIEPYAICOM25 Rev: A0 Z1000 Bypass Option PROFINET SI-EP3 Technical Manual
Description
Description
Values
Default: 0 s
Min.: 0
Max.: 300
Default: 0
Range: 0 to FFFF
Default: 0
Range: 0 to FFFF
Value Range
0 to 255
0 to 255
0 to 255
10: 10 Mbps
100: 100 Mbps
0: Half, 1: Full
10: 10 Mbps
100: 100 Mbps
0: Half, 1: Full

Advertisement

Table of Contents
loading

Table of Contents