Advertisement

5 Installation Procedure
n
Models Z1B1D088 to D273 and Z1B1B096 to B302
1.
Turn the disconnect handle to the "OFF" position and wait the appropriate amount of time for voltage to dissipate.
Verify using a multimeter and follow all appropriate lockout/tagout procedures.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option, bypass, and
circuit boards. Failure to comply may result in ESD damage to circuitry.
2.
Turn the flat head screw fasteners on the front cover 1/2 turn counter-clockwise.
16
Figure 8 Disconnect Power
Figure 9 Turn Front Cover Fasteners
YASKAWA SIEPYAICOM25 Rev: A0 Z1000 Bypass Option PROFINET SI-EP3 Technical Manual