Section 4 Iec 60870-5-103 Parameters And Diagnostics; Parameter List - ABB Relion 615 series Manual

Iec 60870-5-103 communication protocol
Hide thumbs Also See for Relion 615 series:
Table of Contents

Advertisement

1MRS756710 C
Section 4
4.1
Table 10:
IEC 60870-5-103 settings
Parameter
Values (Range)
Serial port 1
0=Not in use
1=COM 1
2=COM 2
Address 1
1...255
Start delay 1
0...20
End delay 1
0...20
DevFunType 1
0...255
UsrFType 1
0...255
UsrInfNo 1
0...255
Class1Priority 1
0=Ev High
1=Ev/DR Equal
2=DR High
Frame1InUse 1
-1=Not in use
0=User frame
1=Standard frame 1
2=Standard frame 2
3=Standard frame 3
4=Standard frame 4
5=Standard frame 5
6=Private frame 6
7=Private frame 7
Frame2InUse 1
-1=Not in use
0=User frame
1=Standard frame 1
2=Standard frame 2
3=Standard frame 3
4=Standard frame 4
5=Standard frame 5
6=Private frame 6
7=Private frame 7
Table continues on next page
615 series
Communication Protocol Manual
IEC 60870-5-103 parameters and diagnostics
IEC 60870-5-103 parameters and
diagnostics

Parameter list

The IEC 60870-5-103 parameters can be accessed with PCM600 or via the LHMI
path Configuration/Communication/IEC 60870-5-103.
Unit
Step
char
char
Default
Description
0=Not in use
COM port for instance 1
1
Unit address for instance 1
4
Start frame delay in chars for instance 1
4
End frame delay in chars for instance 1
9
Device Function Type for instance 1
10
Function type for User Class 2 Frame
for instance 1
230
Information Number for User Class2
Frame for instance 1
0=Ev High
Class 1 data sending priority
relationship between Events and
Disturbance Recorder data.
6=Private frame 6
Active Class2 Frame 1 for instance 1
-1=Not in use
Active Class2 Frame 2 for instance 1
Section 4
27

Advertisement

Table of Contents
loading

Table of Contents