Time Synchronization; Disturbance Recorder File Transfer; Disturbance Recorder File Directory (Asdu 23) - ABB Relion 615 series Manual

Iec 60870-5-103 communication protocol
Hide thumbs Also See for Relion 615 series:
Table of Contents

Advertisement

1MRS756710 C
3.4.3
3.5
3.5.1
615 series
Communication Protocol Manual
Compatibility level (COL) = 2
Eight character ASCII ID string
Internal code = 4 octets
The eight character ASCII string is of format 615xExx<space>.
Value 615 and the E character are constant. It stands for 615 series.
The next four characters identifies the IED type and the variant within the IED
type. For example 615FE02 means REF615 variant FE02 (standard
configuration B).
The last character (space = ASCII 20H) is not used.

Time synchronization

Time synchronization over IEC 60870-5-103 is supported. This requires that the
IED's global Time Sychronization Source parameter (in Configuration/Time/
Synchronization/Synch source) is set to "IEC 60870-5-103" mode. If some other
time synchronization source is configured for the IED, the IEC 60870-5-103 time
synchronization messages will be rejected.

Disturbance recorder file transfer

The IED includes a functionality that converts the IED's natively captured
disturbance file contents into IEC 60870-5-103 disturbance data. Disturbance files
are also available as standard COMTRADE files through PCM600 or WHMI.
IEC 60870-5-103 disturbance recorder spontaneous Class 1 notification message
(disturbance recorder file directory ASDU 23) can be enabled or disabled via the
setting parameter DREnable n located via LHMI path Configuration/
Communication/IEC 60870-5-103/DREnable n. The default setting is disabled.
Purpose of this notification message is to inform the IEC 60870-5-103 client that
the disturbance file directory has been updated. Usually this means that a new
disturbance recording has been captured and stored by the system. If a disturbance
recorder file transfer is not required from the IED, the notification is also unnecessary.

Disturbance recorder file directory (ASDU 23)

The disturbance recorder files IEC 60870-5-103 identification in the IED is a
sequential 16 bit number starting from 1 at IED reset and is incremented for each
new captured disturbance recorder file.
IEC 60870-5-103 standard defines the disturbance recorder file
identification to be the fault number (FAN), which is the same
number that will be generated by ASDU 2 Class 1 events during the
same fault. The IED could theoretically capture several disturbance
recorder files during the same fault, be triggered by a non-
Vendor-specific implementation
Section 3
21

Advertisement

Table of Contents
loading

Table of Contents