Section 4 Iec 60870-5-103 Parameters And Diagnostics; Parameter List - ABB RELION 620 Series Communication Protocol Manual

Hide thumbs Also See for RELION 620 Series:
Table of Contents

Advertisement

1MRS757647 C
Section 4
4.1
Table 14:
IEC 60870-5-103 settings
Parameter
Values (Range)
Operation
Serial port
Address
Start delay
End delay
DevFunType
UsrFunType
UsrInfNo
Class1Priority
Class2Interval
Frame1InUse
Table continues on next page
620 series
Communication Protocol Manual
IEC 60870-5-103 parameters and
diagnostics

Parameter list

The IEC 60870-5-103 parameters can be accessed with PCM600 or via the LHMI path
Configuration/Communication/IEC 60870-5-103/I3C0n.
Some parameters are not visible in the "Basic" setting visibility mode.
To view all parameters use "Advanced" setting visibility mode in the
Parameter Setting tool in PCM600 and LHMI.
Unit
1=on
5=off
1=COM 1
2=COM 2
1...255
0...20
char
0...20
char
0...255
0...255
0...255
0=Ev High
1=Ev/DR Equal
2=DR High
0...86400
s
-1=Not in use
0=User frame
1=Standard frame
1
2=Standard frame
2
3=Standard frame
3
4=Standard frame
4
5=Standard frame
5
6=Private frame 6
7=Private frame 7
IEC 60870-5-103 parameters and diagnostics
Step
Default
5=off
1=COM 1
1
1
1
4
1
4
1
9
1
10
1
230
0=Ev High
1
30
6=Private frame 6
Section 4
Description
Selects if this protocol instance is enabled
or disabled
COM port
Unit address
Start frame delay in chars
End frame delay in chars
Device Function Type
Function type for User Class 2 Frame
Information Number for User Class2
Frame
Class 1 data sending priority relationship
between Events and Disturbance
Recorder data.
Interval in seconds to send class 2
response
Active Class2 Frame 1
31