General Specifications; Safety Specifications - AEMC 1015 User Manual

Megohmmeter
Hide thumbs Also See for 1015:
Table of Contents

Advertisement

3.2

General Specifications

Power Supply: Four 1.5 V AA batteries
Dielectric Test: 6000V, 50/60 Hz, 1 minute
Meter Movement: Rugged taut band suspension
Dimensions: 6.6 x 4.2 x 2.2" (167 x 106 x 55mm)
Weight: 1.45 lbs (650 g)
Operating Temperature Range: 14° to 131°F (-10° to 55°C), 20-80% RH
Storage Range: -40° to 158°F (-40° to 70°C), 10-90% RH
Terminals: "-" Line (black); "+" earth (red); accepts 4mm banana plugs
Reference Conditions: 63° to 73°F (17° to 23°C), 45-55% RH; Supply Voltage: 5.3 to 5.7V;
Voltage Frequency: 45 to 65Hz; Electric Field: <1V/M; Magnetic Field: <40A/M; Position:
Horizontal ± 5°.
3.3

Safety Specifications

IEC 1010-1: Safety requirements for electrical equipment for measure-
ment, control and laboratory use
VDE 0413-1: Insulation testers
VDE 0413-4: Ohmmeters
VDE 0100: Specifications for the creation of high current installations of
nominal voltage less than 1000V
IEC 801: Electromagnetic compatibility for measurement and control
equipment in industrial processes
Part 2: Sections relating to electrostatic discharges
Part 3: Sections relating to radiated electric fields
Part 4: Sections relating to electrostatic discharges
Part 5: Sections relating to electric shocks
IEC 68.2.6: Vibrations
IEC 68.2.27: Shocks
IEC 68.2.29: Shakes
IEC 68.2.31: Bumps
IEC 68.2.32: Free fall
UL 94: Self-extinguishing capability
Specifications are subject to change at any time without notice
8
Megohmmeter Model 1015