T = Flue terminal
I = Mechanical air inlet
a
-
Below eaves, balconies or other projections:
Appliances to 50 MJ/h input ................................................................................................ 300
Appliances over 50 MJ/h input ............................................................................................ 500
b
-
From the ground or above a balcony ..................................................................................... 300
c
-
From a return wall or external corner ..................................................................................... 500
d
-
From a gas meter (M) ........................................................................................................... 1000
e
-
From an electricity meter or fuse box (P) ............................................................................... 500
f
-
From a drain or soil pipe ........................................................................................................ 150
g
-
Horizontally from any building structure (unless appliance approved
for closer installation) or obstruction facing a terminal ......................................................... 500
h
-
From any other flue terminal, cowl, or combustion air intake ............................................... 500
j
-
Horizontally from an openable window, door, non-mechanical air
inlet, or any other opening into a building, with the exception of
sub-floor ventilation:
Appliances up to 150 MJ/h input ......................................................................................... 500
Appliances over 150 MJ/h input ........................................................................................ 1500
k
-
From a mechanical air inlet, including a spa blower ......................................................... 1500
n
-
Vertically below an openable window, non-mechanical air
inlet or any other opening into a building, with the exception of ................................. See table
sub-floor ventilation ............................................................................................................ below
Space heaters
Up to 50 MJ/h
input
150
NOTES:
1. All distances are measured vertically or horizontally along the wall to a point
in line with the nearest part of the terminal.
2. Prohibited area below electricity meter or fuse box extends to ground level.
3. See clause 5.13.6.6 for restrictions on a flue terminal under a roofed area.
4. See Appendix J, Figure J1(a) and J2(a) for clearances required from a flue
terminal to a LP Gas cylinder. A flue terminal is considered to be a source of ignition.
MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE TERMINALS
FIGURE 4
M = Gas meter
P = Electricity meter or fuse box
CLEARANCES 'n' (mm)
UP to 50 MJ/h
input
500
OR THE FLUE TERMINALS OF OUTDOOR APPLIANCES
MIN. CLEARANCE (mm)
All other appliances
Over 50 MJ/h &
up
to 150 MJ/h
1000
7
Shading indicates prohibited
areas for flue terminals
Over 150 MJ/h
input
1500