Heat-N-Glo SL-550TRS-AUC Installation And Operation Instructions Manual page 34

Table of Contents

Advertisement

SYMPTOM
IV. Frequent pilot outage
problem.
POSSIBLE CAUSE
C. Defective valve.
D. Plugged burner orifice.
E. Wall switch, or wires defective.
A. Pilot flame may be too high or too
low, or blowing (high), causing
pilot safety to drop out.
34
CORRECTIVE ACTION
With the pilot in the ON posi-
tion, disconnect the thermopile
leads from the valve. Take a
reading at the thermopile leads.
The reading should be 325 mil-
livolts minimum. Replace the
thermopile if the reading is be-
low the minimum.
1. Turn valve knob to "ON". Place
ON/OFF switch to "ON". Check
with millivolt meter at thermo-
pile terminals. Millivolt meter
should read greater than 100
m.v. If the reading is okay and
the burner does not come on,
replace the gas valve.
1. Check burner orifice for stop-
page and remove.
1. Follow corrective action in A.1
above; check switch and wiring.
Replace where defective.
1. Clean and adjust pilot flame for
maximum flame impingement
on the thermocouple. Follow
lighting instruction carefully.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents