Signal Output And Test Options; Signal Output Delay; Test Function - Siemens sitrans LVS200 Instruction Manual

Standard vibrating level switch for use in all liquid and slurry applications
Hide thumbs Also See for sitrans LVS200:
Table of Contents

Advertisement

Available languages

Available languages

Signal output and test options

The signal output and test options listed below apply only to specific power
Note:
supply options.

Signal Output Delay

Universal voltage (DPDT) model
The signal output can be delayed and is adjustable from 0 to 30 seconds. Turn the
potentiometer clockwise to increase the delay time.
Potentiometer T1: Delay when output switches from fork covered to uncovered.
Potentiometer T2: Delay when output switches from fork uncovered to covered.

Test function

NAMUR model (IEC 60947-5-6) and 8/16 mA or 4 to 20 mA model
If the fork is uncovered, pressing this button will stop the vibration and the signal output
will switch to indicate a covered fork. You can test the vibration and the electronics
without removing the LVS200 from the vessel. If the fork is covered, pressing the button
has no effect.
NAMUR model
Test button
Page EN-14
Electronic module
SITRANS LVS200 – INSTRUCTION MANUAL
diagnostic LED
sensitivity adjustment:
B = factory setting
A = decreased sensitivity
7ML19985FT62