The CP 521 BASIC is a powerful peripheral module that can be used with the SIMATIC systems S5-
90U, S5-95U and the S5-100U. It has its own central processor (cannot be used with the CPU 100,
6ES5 100-8MA01).
A separate manual for this module is available. The order number is 6ES5 998-0UW21.
A brief overview of the functions of this module follows.
Function
This module comes with a special COM software package that is required for generating and storing
BASIC programs (on a floppy disk or an EPROM submodule).
Since the CP 521 includes a basic interpreter, you can create and run BASIC programs that
exchange data with a CPU and a connected peripheral device. Use a programmer or a PC terminal
and the COM software to program the BASIC interpreter.
You can store the BASIC programs in the module's own battery backed-up RAM or on a memory
submodule that can be plugged in.
Connect programmers or PC terminals to the CP 521 via a serial interface. You can choose (by
setting parameters) between a passive TTY current-loop interface or a RS-232 C V.24 interface to
connect a programmer or terminal. Connect a printer to the unidirectional V.24 interface of the
module to print listings or messages.
Change parameter settings for the peripheral interface by using a BASIC command or by using the
BASIC program.
The CP 521 has an integral real-time clock that can be backed up by a battery. You can use the
clock data in unidirectional data traffic to log process statuses or process malfunctions.
Installation
Install the CP 521 BASIC communications module on the bus module like any other I/O module
(see section 3)
With the S5-90U, a maximum of 1 communications module (limited by current consumption) can
be plugged in only at slots 0 to 5.
With the S5-95U, a maximum of 5 communications modules (limited by current consumption)
can be plugged in only at slots 0 to 7.
The module has no connection to the terminal block.
Connect the printer to the module via a 25-pin sub-D female connector.
Addressing
The module is addressed like a 4-channel analog module.