Siemens SIMATIC S5-90U System Manual page 464

Table of Contents

Advertisement

Module Spectrum
Connection of the Module
Figure 15-21 shows how to connect loads to the current outputs of the module.
1
3
2
+
L
M
24 V DC
(4/8)
QI
R
L
Figure 15-21. Connection via a Two-Wire Circuit (6ES5 470-8MC12)
Analog Value Representation
Table 15-36. Analog Output Module 470-8MC12 (Unipolar)
Units
Output Values
in mA
1280
24.0
1025
20.016
1024
20.0
512
12.0
1
4.016
0
4.0
- 1
3.984
- 256
0.0
- 512
- 4.0
- 1024
- 12.0
- 1280
- 16.0
15-98
5
7
9
10
4
6
8
Terminal assignment
(6/10)
M
Terminals
ANA
High Byte
0
1
0
1
0
0
0
0
1
0
0
0
0
0
0 1 0 0 0 0 0 0 0 0 0 0 x x x x
0 0 1 0 0 0 0 0 0 0 0 0 x x x x
0 0 0 0 0 0 0 0 0 0 0 1 x x x x
0 0 0 0 0 0 0 0 0 0 0 0 x x x x
1 1 1 1 1 1 1 1 1 1 1 1 x x x x
1 1 1 1 0 0 0 0 0 0 0 0 x x x x
1 1 0 0 0 0 0 0 0 0 0 0 x x x x
1 1 0 0 0 0 0 0 0 0 0 0 x x x x
1 0 1 1 0 0 0 0 0 0 0 0 x x x x
Key:
QI:
Analog output " Current"
M
:
Chassis ground terminal of
ANA
the analog unit
Low Byte
0
0
0
0
0
x
x
x
x
0
0
0
0
1
x
x
x
x
S5-90U/S5-95U
Range
Overrange
Nominal range
Overrange
EWA 4NEB 812 6115-02b

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s5-95u

Table of Contents