Function Modules
Function
SIMATIC S5-90U and SIMATIC S5-95U offer different solutions for individual closed-loop control
(PID) tasks. First there is a software solution via function blocks (only for the S5-95U) and second,
a control module (for example, a module that can solve PID control tasks simply and in a time saving
manner). The basis, in both cases, is a PID-control algorithm.
The IP 262 closed-loop control module can be used with any of the S5-90U, S5-95U, and S5-100U
programmable controllers. It can be used without COM software.
The module relieves the programmable controller from closed-loop control tasks. The IP 262 also
works with its own power supply in a stand-alone operation. The module can function independently
without a programmable controller and can handle up to four closed-loop control circuits.
Two interfaces are located on the front panel of the module.
An interface for the connection of a programmer (PG) or an operator panel (OP) or the
SINEC L1 Network (under development)
An interface for the connection of analog and binary inputs
In addition, the following items are available.
A selector switch for each channel for current and voltage (thermocouples or PT 100)
A status LED for RUN (a continuously lit green light), transducer malfunction (blinking light), and
module malfunction (off)
Additionally, the module offers the following inputs.
4 analog inputs for direct feed of setpoint and actual values
4 binary inputs for control variables
The module is well-suited to take over control-loop tasks in the area of industrial processing
technology, for example, temperature control, pressure and flow control, continuous injection
functions, and non-time-critical closed-loop speed controls.
Modules
There are two IP 262 modules.
... - 8MA 12 with 3 analog outputs for continuous controllers with analog output signals
... - 8MB12 with 8 binary outputs for continuous controllers with pulse time interval signals for
step-action controllers