Siemens SIMATIC S5-90U System Manual page 192

Table of Contents

Advertisement

STEP 5 Operations
Off-Delay
Example:
When input I32.0 is reset, output Q32.5 is set to zero after a certain delay (t). The value in FW14
specifies the delay time.
Timing Diagram
Signal states
1
0
1
0
t
STL
A
I
32.0
L
FW
14
SF
T
5
I32.0
NOP 0
FW14
NOP 0
NOP 0
A
T
5
=
Q
32.5
8-24
I32.0
Q32.5
Time in s
t
CSF
T 5
0
T
TV
BI
DE
R
Q
Q32.5
S5-90U/S5-95U
Circuit Diagram
I32.0
T 5
Q32.5
LAD
T 5
I32.0
0
T
FW14
TV
BI
DE
R
Q
Q32.5
EWA 4NEB 812 6115-02b