S5-90U/S5-95U
5
Diagnostics and Trouble Shooting
5.1
Diagnostic Byte
The diagnostic byte offers you another means of controlling the process sequence.
The diagnostic byte displays the following:
Whether a counter has reached the comparison value (counter overflow)
Whether and where an interrupt was triggered
Whether the power supply for the onboard I/Os has failed (only for the S5-95U)
Whether a battery backup is available (only for the S5-95U)
The diagnostic byte for both programmable controllers is in input byte (IB) 35.
Diagnostic Byte Assignment for the S5-90U
Interrupt at I 33.0
No interrupt at I 33.0
Counter overflow
No counter overflow
X=insignificant
Signal status "1" in one of the diagnostic bits signifies that:
Since the last start-up, an interrupt has occurred. This does not mean that interrupt processing
is taking place.
Signal status"0" in one of the diagnostic bits signifies one of the following conditions.
Since the last start-up, no interrupt has occurred.
The user erased the respective diagnostic bit after the interrupt. It does not signify that the
corresponding interrupt processing is complete.
EWA 4NEB 812 6115-02b
Bit no.:
7
IB 35
X
1
0
1
0
Figure 5-1. Diagnostic Byte for the S5-90U
Diagnostics and Trouble Shooting
6
5
4
3
2
i
X
X
X
X
1
0
C
X
5-1