Interface Features

MicroTech Network

Control sequencing, stop/start, equipment protection
monitoring, and fault resets can be accomplished through a
network connection. The following unique values and
parameters can be accessed for each unit (refer to Protocol
Document ED15054 for more information):
• Return air and discharge air temperatures
• Compressor, fan and reversing valve status
• High pressure, low temperature, brownout and drain pan
status
• Occupied and unoccupied heat and cool set points
• Auto/manual and occupied/unoccupied fan control
• Mode, fault, system, schedule and set point operation
• Compressor starts and fan run hours
• Load shed level (L
W
ON
• Tenant override status
In addition, the following unique operation and maintenance
parameters can display for each unit:
• Leaving water temperature
• Return air temperature set point (wall sensor adjustment)
• Adaptive optimal start (L
• Occupied/unoccupied (on/cycle) fan mode
• Room temperature warning
• Filter changes from fan hours
• Compressor management: on/off differential, minimum off
time, minimum on time
Communications Failure (L
communication link fails for any reason, the affected WSHP
controller remains operational. Its operating mode will be the
last received over the network unless power is cycled, and then
it defaults to occupied. Its minimum position, heating, and
cooling set points will be those last received over the network,
regardless of whether power is cycled.
Communications Failure (L
communication link fails for any reason, the affected WSHP
controller remains operational. The status of its heating and
cooling set points as well as its occupancy and other network
adjustable settings depends upon whether the BAS is using
L
W
bindings with associated heartbeats.
ON
ORKS

Wall-Mounted Sensor

There are four optional wall sensor packages available. All
include a remote status LED and tenant override button. Set
point adjustment and thermometer are optional features.
McQuay IM 660-3
only)
ORKS
W
only)
ON
ORKS
W
): If the network
ON
ORKS
M
): If the network
ON
ARK
The wall-mounted sensor must be field installed and field
wired to the water source heat pump. Terminal Board #1
provides the connections for all room temperature sensor field
wiring. Refer to the unit wiring diagram provided and to IM
529, MicroTech Room Temperature Sensors, for information
on wall sensor package installation.
Figure 5: Wall-mounted temp sensor wiring
WSHP
Sensor LED
TB1-1

Tenant override

TB1-2
Sensor input
TB1-3
Sensor common
TB1-4
Table 4: Maximum wire length to sensors
Gauge
18 AWG
20 AWG
22 AWG

Remote Room Set Point Adjustment

The remote set point adjustment potentiometer allows the room
set point to be adjusted up or down by as much as 3°F (1.7°C).
It is available with several of the optional wall sensor packages.
Tenant Override
A wall-mounted tenant override switch is standard on all McQuay
MicroTech Room Temperature Sensors. Pressing and holding the
tenant override button for 1.0 to 6.0 seconds puts the unit into
tenant override mode for a set time period (default = 60 minutes).
Press the tenant override button again for 1.0 to 6.0 seconds and
the unit returns to unoccupied mode by default. A separate
configuration property is available that allows users to extend the
tenant override period for up to 60 minutes with a second button
press. Except for the fact that it is temporary, the tenant override
operating mode is identical to the occupied operating mode.
L
W
only: Pressing and holding the tenant override
ON
ORKS
button for at least 6 seconds but not more than 10 seconds
activates the network "query address" mode, indicating the
unit address in question at the MicroTech gateway panel.
L
W
only: Pressing and holding the tenant override
ON
ORKS
button more than 10 seconds activates the network
"self-configure" mode, requesting the assignment of the next
sequential address from the MicroTech gateway panel.
L
M
only: Similar to pressing the service pin, pressing
ON
ARK
and holding the tenant override button for more than 10
seconds causes the Neuron chip to broadcast a message over
the L
W
network containing its unique 48-bit Neuron
ON
ORKS
ID. This is useful during network commissioning.
Wall sensor
Red
Green
White
Black
Length (ft.)
625
380
260
5