CHAPTER 8 - SPECIFICATION
Display/Alarm Point:
Linearity:
Repeatability:
Remote Facilities:
Remote Inhibit / Reset Inputs
Active For Inputs:
Maximum Input Voltage:
Maximum Input Current:
DC Supply:
Electronic Drift:
Dimensions:
Weight:
5.4

Four Channel Control Card - Catalytic

Power Consumption:
Drive:
Initial Accuracy:
Current Adjustment:
Maximum Drive Voltage:
Protection:
Maximum Line Resistance:
Full Scale Signal Range:
Bridge Imbalance Default Limits: ±100mV from centre at 2V bridge
Adjustment:
±2% fsd.
±2% fsd.
Inhibit/Alarm Reset.
More than 2V.
32V.
5mA.
18V to 32V dc.
Less than ±3% / 6 months.
Height:
Width:
Depth:
170g.
12.8W (maximum at 200mA sensor
current).
8.5W (typical).
Constant Current.
±1%.
Electronic in 1mA stepsfrom 90 to
315mA.
10V.
Protected against short circuit and
open circuit.
40 ohms (including sensor) at
200mA.
15mV to 300mV.
voltage.
Electronic adjustment of bridge
balance and signal gain.
8-6
5704 Control System
132mm.
25mm.
172mm.