3-7-2 FUNDAMENTAL FUNCTIONS

1. FGL remote/controller connection
Air conditioning
control system
Intake temperature control
(SET3-3)
Intake temperature (Room temperature)
Set temperature
Cooling: 18 to 30°C
objective
Heating: 10 to 30°C
Cooling
Thermostat OFF
Intake temperature < Setting temperature -0.5°C
conditions
Heating
Intake temperature > Setting temperature +0.5°C
Operation
(ON/OFF/Mode/
FGL controller
Set temperature
Fan control
Fan control commands are output from the DX kit external output terminal
2. External controller connection
Air conditioning
control system
Intake temperature control
(SET3-3)
Analog input
Set temperature input / Capacity input
system (SET3-2)
Selection
Temperature
Intake temperature (Room temperature)
Setting range
Cooling: 18 to 30°C
Heating: 10 to 30°C
Thermostat
Cooling
OFF conditions
Intake temperature < Setting temperature -0.5°C
Heating
Intake temperature > Setting temperature +0.5°C
0%, 5% to 100%
Capacity
input range
Controlled by external controller and EEV closed by making the capacity input 0% in cooling mode.
Thermostat OFF
EEV slightly opened when the Compressor operating in heating mode.
conditions
Operation
Controlled by external controller, input to DX Kit external input terminal
(ON/OFFMode/
*Operation from FGL controller is disabled.
Set temperature
(Only monitoring is possible)
When error
When fanmotor locked or another error was generated at the external equipment, the refrigerant cycle is
generated at
stopped by inputting an error signal to the DX Kit external input terminal. (EEV is Closed)
external equipment
Fan control
Control is perfomed by external equipment, but when you want to stop the fan during defrosting, use the
defrost signal that is output from the DX Kit external output terminal.
Discharge temperature control
Discharge temperature
Cooling: 14 to 25°C
Heating: 17 to 28°C
Cooling
Discharge temperature < Setting temperature -5.0°C
Heating
Discharge temperature > Setting temperature +5.0°C
for 5 minutes
Outlet temperature control
Set temperature input / Capacity input
Selection
Discharge temperature
Cooling: 14 to 25°C
Heating: 17 to 28°C
Cooling
Discharge temperature < Setting temperature -5.0°C
Heating
Discharge temperature > Setting temperature +5.0°C
for 5 minutes
03-19