Fujitsu AUXB04GALH Service Manual page 109

Airstage v-iii
Hide thumbs Also See for AUXB04GALH:
Table of Contents

Advertisement

Trouble shooting 23
INDOOR UNIT Error Method:
Indoor unit Heat Ex. outlet temp.
Sensor Error
Detective Actuators:
Indoor Unit Controller PCB Circuit
Heat Exchanger Outlet Temp. Sensor
Forecast of Cause :
1. Connector defective connection
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if Sensor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check sensor resistance value
Sensor Characteristics (Rough value)
Temperature (
°F)
Temperature (
°C)
Resistance Value (k )
Voltage Value (V)
Temperature (
°F)
Temperature (
°C)
Resistance Value (k )
Voltage Value (V)
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Corresponding connector
Model Type
Duct type
Cassette type
Wall mounted type
Floor / Ceiling type
Compact Wall mounted type
If the voltage does not appear, replace Controller PCB and set up the original address.
Indicate or Display:
E42. 3
Outdoor Unit : E.5 U.1
Indoor Unit
Error Code
Detective details:
When open or shorted Heat Exchanger outlet temp. sensor is detected
2.Sensor defective
32
41
50
0
5
10
168.6
129.8
100.9
1.14
1.39
1.65
104
113
122
40
45
50
26.3
21.6
17.8
3.27
3.49
3.69
Heat Ex Outlet temp. Sensor
(Gray Wires)
CN9
CN21
: Operation LED 4 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
: 4 2
3.Controller PCB defective
59
68
77
15
20
25
79.1
62.5
49.8
1.93
2.22
2.50
04-33
86
95
30
35
40.0
32.4
2.77
3.03
DC

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents