Fujitsu AUXB04GALH Service Manual page 26

Airstage v-iii
Hide thumbs Also See for AUXB04GALH:
Table of Contents

Advertisement

1-7 Field Setting / Function Setting for Indoor unit
Classification
Indoor unit field setting
Address
setting by
Filter
remote controller
Airflow
Correction
Change of
Function 1
*1: Auto restart is an emargency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2: Fan Setting when cooling thermostat OFF, Connection of the wired remote controller (2-wire type or 3-wire type) and switching its thermistor are necessary.
ITEM
Setting Mode
CODE No.
01
Indoor unit address
02
Refrigerant circuit address
11
Filter indicator Interval
13
Filter sign display
20
Ceiling airflow
(Cassette type only)
23
Vertical airflow direction
24
Horizontal swing airflow direction
26
Static Pressure setting
- Slim Duct Only -
The Range of static pressure is
different from one model to other.
30
Cool air temperature trigger
31
Heat air temperature trigger
32
Temperature correction in Auto
40
Auto restart *1
43
Cool air prevention
46
External control
47
Error report target
49
FAN Setting when cooling thermo-
stat OFF *2
ITEM
CODE No.
00~63
00~63
00~99
00~99
00
Default
Longer
01
02
Shorter
00
Enable
01
Disable
02
Display only on central remote control
00
Default
01
High ceiling
00
Default
01
Raise
00
Default
01
Left half
02
Right half
00
0 Pa
01
10 Pa
02
20 Pa
03
30 Pa
04
40 Pa
05
50 Pa
06
60 Pa
07
70 Pa
08
80 Pa
09
90 Pa
31
25 Pa (Standard)
00
Default (0 °C )
01
Temperature overshoot setting (+2 °C)
02
Temperature undershoot setting (-2 °C)
00
Default (0 °C )
01
Temperature undershoot setting (-6 °C)
02
Temperature slightly undershoot setting (-4 °C)
03
Temperature overshoot setting (+4 °C)
00
Disable
01
Enable (Nonfunctional on J2 Series)
00
Enable
01
Disable
00
Super low
01
Follow the setting on the remote controller
00
Start / Stop
01
Emergency stop
02
Foreced stop (Start/Stop by RC is restricted)
00
All
01
Display only for central remote control
00
Follow the setting on the remote controller
01
Foreced stop
01-21
Setting Function
Model name
Range of static pressure
ARXD04
ARXD07/09/12/14
0 to 90 Pa
ARXD18
ARXD24
0 to 50 Pa
Default
00
00