Fujitsu AUXB04GALH Service Manual page 233

Airstage v-iii
Hide thumbs Also See for AUXB04GALH:
Table of Contents

Advertisement

AJ*108/ 126/ 144/ 162LALBH, AJ*108/ 126/ 144/ 162LATBH
Inverter PCB
Screws
(For IPM)
Remove the 2 mounting screws.
Note the tightening torque at the installation.
Tightening torque is as follows.
- Temporary tightening : 0.3 +0.1N m
-
- Final tightening
: 1.5 +0.1N m
-
IPM
Spread the heat dissipation compound on the other side of IPM
when you exchange Inverter PCB by the repair.
Remove the 5 mounting screws and codes.
Remove the mounting screw
and code.
.
.
Compound
Parts Name
HEAT SINKER(20g)
06-07
Screws
(For Capacitor)
Screws
(For Magnetic relay)
Remove the connectors
and spacers.
Service Parts No.
0000036795
Screws
(For CT PCB)
Spacers
(4 places)