Fujitsu AUXB04GALH Service Manual page 199

Airstage v-iii
Hide thumbs Also See for AUXB04GALH:
Table of Contents

Advertisement

SERVICE PARTS INFORMATION 19
Indoor Unit AC Fan Motor
Check Point : ARXC36GATH (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
150°C
Pr
Check Point : ARXC45/ 60GATH (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
145°C
Pr
Check Point : ARXC72GATH (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
145°C
Pr
Check Point : ARXC90GATH (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
145°C
Pr
BLUE (Low)
VIOLET (Med)
RED (Hi)
BLACK
(AC)
WHITE
BLUE (Low)
VIOLET (Med)
RED (Hi)
(AC)
BLACK
WHITE
BLUE (S-Lo)
VIOLET (Lo)
PINK (Med)
RED (Hi)
(AC)
BLACK
WHITE
BLUE (S-Lo)
VIOLET (Lo)
PINK (Med)
RED (Hi)
(AC)
BLACK
WHITE
04-123
Lead wire
Resistance value
White Red
13.4
Red
Black
16.9
11.5
Red
Violet
Violet
Blue
13.3
Lead wire
Resistance value
6.84
White Red
9.78
Red
Black
6.1
Red
Violet
Violet
Blue
6.1
Lead wire
Resistance value
White Red
5.25
Red
Black
5.02
Red
Pink
1.86
Pink
Violet
0.94
0.94
Violet
Blue
Lead wire
Resistance value
White Red
4.24
4.16
Red
Black
Red
Pink
0.46
Pink
Violet
0.91
Violet
Blue
0.46
8%
8%
8%
8%
at 20°C
7%
7%
7%
7%
at 20°C
7%
7%
7%
7%
7%
at 20°C
7%
7%
7%
7%
7%
at 20°C