Fujitsu AUXB04GALH Service Manual page 167

Airstage v-iii
Hide thumbs Also See for AUXB04GALH:
Table of Contents

Advertisement

Trouble shooting 82
INDOOR UNIT Error Method:
Indoor unit suction air temp.
thermistor error
Detective Actuators:
Indoor Unit Controller PCB Circuit
Suction air temp. thermistor
Forecast of Cause :
1. Connector defective connection
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check sensor resistance value
SensorCharacteristics (Rough value)
Temperature (
°F )
Temperature (
°C )
Resistance Value (
Temperature (
°F )
Temperature (
°C )
(
Resistance Value
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage CN9 of Controller PCB (DC5.0V)
If the voltage does not appear, replace Controller PCB and set up the original address.
E 4A.1
Indicate or Display:
Outdoor Unit : E.5 U.1
Error Code
Detective details:
When Indoor unit suction air temp. thermistor open or shortage is detected.
2. Thermistordefective
32
41
50
0
5
10
)
33.6
25.2
20.1
104
113
122
40
45
50
)
5.3
4.3
3.5
: 4 A, 4 A. 1
3. Controller PCB defective
59
68
77
15
20
25
15.8
12.5
10.0
04-91
86
95
30
35
8.0
6.5
DC