6.1.1 Initialization procedure for force-locking actuators

1. Select variable, enter value "3" for command "manual down", press the return key and
wait for the actuator to move to zero position.
2. Enter value "1" for command "manual stop" and press the return key.
3. Enter value "88" for command "initialization 0 %" and press the return key.
4. Enter value "2" for command "manual up" and press the return key. Wait until the
actuating time of the actuator has elapsed (6 mm = 35 s, 12 mm = 70 s).
5. After the actuating time has elapsed, enter value "1" for command "manual stop" and
press the return key.
6. Enter value "77" for command "initialization 100 %" and press the return key.

6.1.2 Initialization procedure for form-fit actuators

1. Enter "99" and press the return key or press the initialization button of the actuator.
Note:
The activation of any of the initialization commands "77, 88 and 99" causes the operating
mode to be automatically set to automatic operation.
Description of closed loop actuator object
15
EB 5824-1 EN