Description of closed loop actuator object
6.1. Description of network variables
Variable
nviSoll
nvoSollFb
nvoSollPosi
nvolstPosi
nvoMinMax
ST_OFF
ST_LOW
ST_MED
ST_HIGH
ST_ON
nvoStellAusg
ST_OFF
ST_HIGH
ST_LOW
nvoSicher
ST_OFF
ST_ON
nvoElapsedTime
nvoMotorTime
nviAuswahl
0
1
2
3
77
88
99
14
EB 5824-1 EN
Type
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_disc
SNVT_lev_disc
SNVT_lev_disc
SNVT_time_sec
SNVT_time_sec
unsigned char
Function
Set point input of position 0 to 100 %
Feedback of set point input
Set position calculated from data points
nciMin Rnge, nciMaxRnge and ncilnvert
Actual status of actuator
Output variable of limit value monitoring
istPosi < nciLow2
istPosi < nciLow1
istPosi < nciHigh1
istPosi < nciHigh2
istPosi ≥ nciHigh2
Actual status of actuator
Down
Up
Stop
Feedback of safety monitoring
Absolute uptime of the actuator (s)
Absolute uptime of the motor (s)
Input variable for start-up /manual adjustment
Note: manual adjustment has priority over
standard operation
Automatic
Manual stop
Manual up
Manual down
Acceptance 100 % initialization value
Acceptance 0 % initialization value
Start initialization routine