Description Of Network Variables - Samson 5824 Mounting And Operating Instructions

Electric actuators with lon interface
Table of Contents

Advertisement

Description of closed loop actuator object

6.1. Description of network variables

Variable
nviSoll
nvoSollFb
nvoSollPosi
nvolstPosi
nvoMinMax
ST_OFF
ST_LOW
ST_MED
ST_HIGH
ST_ON
nvoStellAusg
ST_OFF
ST_HIGH
ST_LOW
nvoSicher
ST_OFF
ST_ON
nvoElapsedTime
nvoMotorTime
nviAuswahl
0
1
2
3
77
88
99
14
EB 5824-1 EN
Type
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_disc
SNVT_lev_disc
SNVT_lev_disc
SNVT_time_sec
SNVT_time_sec
unsigned char
Function
Set point input of position 0 to 100 %
Feedback of set point input
Set position calculated from data points
nciMin Rnge, nciMaxRnge and ncilnvert
Actual status of actuator
Output variable of limit value monitoring
istPosi < nciLow2
istPosi < nciLow1
istPosi < nciHigh1
istPosi < nciHigh2
istPosi ≥ nciHigh2
Actual status of actuator
Down
Up
Stop
Feedback of safety monitoring
Absolute uptime of the actuator (s)
Absolute uptime of the motor (s)
Input variable for start-up /manual adjustment
Note: manual adjustment has priority over
standard operation
Automatic
Manual stop
Manual up
Manual down
Acceptance 100 % initialization value
Acceptance 0 % initialization value
Start initialization routine