Technical Specifications - La Marche ULTRA SERIES Installation And Operation Manual

Table of Contents

Advertisement

7.

Technical Specifications

AC input
Voltage and frequency
Rated Current
Input protection
Inrush limiting
Efficiency
Power factor
Input Terminals
Charger output
Nominal voltage rating
Voltage adjustment
Current
Charging characteristic
Line and load
regulation
Output ripple
Temperature
compensation
Output protection
Output Terminals
Status
LED status indicator
indication
Display and
Display
Alarms
LCD Dot Matrix Display
Relay Alarm contacts
Relay Alarm contact
ratings
Alarm Terminals
Environmental
Operating temperature
Storage temperature
Over temperature
protection
Humidity
Physical
Ingress Protection
Dimensions
Weight
Auto ranging 105-264 VAC, 45-65 Hz
2.6A @120VAC, 1.4A @240VAC (for 24V 10A output mode)
AC Fuse (250V, 5A Glass type)
Inrush current limited NTC
Exceeds CEC-400-2012-019-CM requirements
0.9
Terminal blocks (Push-In Springable type); AWG 24 - AWG 12
24 volt nominal or field selectable 12/24-volt
According to selected number of cells/ Battery type and
Volt/cell.
10A at 24V and 20A at 12V
ULTRACAP Mode
Battery Mode
±0.5%
<100mV rms
Enable/ Disable, Remote temperature sensing through probe.
Electronic current limit, Transient protection,
DC fuse (32V, 20A Blade Fuse- Plug-In type)
Terminal blocks (Lockable type); AWG 24 – AWG 10
AC ON (Green LED), Float (Green LED), Equalize (Yellow LED),
Fault (Red LED)
LCD Display (16x2)
Displays volts, amps, Mode of operation and Status messages
Charger Fail, AC Fail, Low DC Voltage, High DC Voltage,
Summary
Rated 2A @ 30 VDC, 0.5A @ 125VAC
Single form C dry type
Spring Cage; AWG 24 - AWG 16
-40°C to 65°C (-40°F to 149°F)
-40°C to 85°C (-40°F to 185°F)
Derates over 50C up to 70C
Above 70C, switches off.
0% to 95% non-condensing
IP-20; NEMA-1
7.9 x 4.1 x 10.7 in
(W x D x H)
801 x 105 x 273 mm
(W x D x H)
6.4 lbs (2.9 Kgs)
15

Advertisement

Table of Contents
loading

Table of Contents