Appendix B
Module Tag Definitions
Table 31 - 5069-IF8 Module - Input Tags
Name
Chxx.CalSuccessful
Chxx.Data
Chxx.RollingTimestamp
Table 32 - 5069-IF8 Module - Output Tags
Name
Chxx.LLAlarmEn
Chxx.LAlarmEn
Chxx.HAlarmEn
Chxx.HHAlarmEn
140
Size
Definition
BOOL
Indicates calibration on this channel is complete and the Calibrating state
has been exited.
This tag remains set after valid calibration as long as connection is open.
IMPORTANT: This tag is available only when you use the Data with
Calibration connection type in the Module Definition. If you use the Data
connection type, this tag does not appear in the module tags.
For more information on how to define a module, see
page 89
REAL
Channel data in scaled Engineering Units.
INT
Continuously-running 15-bit timer that counts in milliseconds.
Whenever an input module scans its channels, it also records the value of
RollingTimestamp at that time.
The user program can then use the last two RollingTimestamp values and
calculate the interval between receipt of data or the time when new data
has been received.

Output Tags

Table 32
describes the 5069-IF8 module output tags.
Size
Definition
BOOL
Enables the Low Low alarm.
IMPORTANT: To use this alarm, you must not only set the tag to 1. You must
also make sure the Chxx.AlarmDisable configuration tag for the same
channel is set to 0.
If the Chxx.AlarmDisable configuration tag is set to 1, that is, alarms are
disabled, this alarm does not work regardless of the tag value.
BOOL
Enables the Low alarm.
IMPORTANT: To use this alarm, you must not only set the tag to 1. You must
also make sure the Chxx.AlarmDisable configuration tag for the same
channel is set to 0.
If the Chxx.AlarmDisable configuration tag is set to 1, that is, alarms are
disabled, this alarm does not work regardless of the tag value.
BOOL
Enables the High alarm.
IMPORTANT: To use this alarm, you must not only set the tag to 1. You must
also make sure the Chxx.AlarmDisable configuration tag for the same
channel is set to 0.
If the Chxx.AlarmDisable configuration tag is set to 1, that is, alarms are
disabled, this alarm does not work regardless of the tag value.
BOOL
Enables the High High alarm.
IMPORTANT: To use this alarm, you must not only set the tag to 1. You must
also make sure the Chxx.AlarmDisable configuration tag for the same
channel is set to 0.
If the Chxx.AlarmDisable configuration tag is set to 1, that is, alarms are
disabled, this alarm does not work regardless of the tag value.
Rockwell Automation Publication 5000-UM005B-EN-P - November 2015
Valid Values
• 0 = Calibration was not
successful
• 1 = One of the following:
– Calibration was successful
and calibrating state has been
exited.
– Calibration data is present
Module Definition on
and applied.
Any positive or negative value.
0 ...32767
Valid Values
• 0 = Alarm is disabled
• 1 = Alarm is enabled
• 0 = Alarm is disabled
• 1 = Alarm is enabled
• 0 = Alarm is disabled
• 1 = Alarm is enabled
• 0 = Alarm is disabled
• 1 = Alarm is enabled