Output Modules - Ac - Allen-Bradley 1746 Series Installation Instructions Manual

Discrete i/o modules, combination input/output module
Table of Contents

Advertisement

Output Modules - ac

Table 12:Specifications for Output Modules 1746-OA8, -OA16, and -OAP12
Specification
Voltage Category
Number of Outputs
Points per Common
Operating Voltage
Backplane Current
Consumption
Max. Signal Delay, Resistive
(5)
Load
Off State Leakage (max.)
Load Current (min.)
Continuous Current per
(7)
Point
Continuous Current
per Module (max.)
On State Voltage Drop (max.)
Surge Current per Point
(max.)
(1) Removable Terminal Block.
(2) A fused common and blown fuse LED are provided on this module. See "Fuse Protection
and Blown Fuse Diagnostics" on page 32.
(3) Use ID Code 2803 when configuring your system with programming software or the HHT.
(4) Certified for Class 1, Division 2 hazardous location by CSA.
(5) Triac outputs turn on at any point in the ac line cycle, and turn off at ac line zero cross.
(6) To limit the effects of leakage current through solid state outputs, a loading resistor can
be connected in parallel with your load. For 120V ac operation, use a 15K Ω, 2W resistor.
For 240V ac operation, use a
15K Ω, 5W resistor.
OA8
8
4
5V dc
0.185A
24V dc
(6)
1.0A at 30°C
0.50A at 60°C
8.0A at 30°C
4.0A at 60°C
1.50V at 1.0A
(8)
10.0A for 25
ms
Discrete I/O Modules
Catalog Number 1746-
(1)
OA16
120/240V ac Signal Input
16
8
85 to 265V ac at 47 to 63 Hz
0.370A
0.0A
on = 1 ms, off = 11.0 ms
2 mA
10 mA
0.50A at 30°C
0.25A at 60°C
8.0A at 30°C
4.0A at 60°C
1.50V at
0.50A
10.0A for 25
ms
Publication 1746-IN005A-US-P
17
(1)(2)(3)
OAP12
(4)
12
6
0.370A
2.0A at 30°C
1.25A at 55°C
1.0A at 60°C
9.0A at 30°C
6.0A at 60°C
1.2V at 2.0A
17.0A for 25
(9)
ms

Hide quick links:

Advertisement

Table of Contents
loading