Input Tags - Allen-Bradley 5069-IF8 User Manual

Analog i/o modules 5000 series in logix5000 control systems
Table of Contents

Advertisement

Table 30 - 5069-IF8 Module - Configuration Tags
Name
Chxx.HHAlarmLimit
Chxx.RateAlarmLimit
Chxx.AlarmDeadband

Input Tags

Table 31 - 5069-IF8 Module - Input Tags
Name
RunMode
ConnectionFaulted
DiagnosticActive
DiagnosticSequenceCount
Chxx.Fault
Size
Definition
REAL
The High High alarm trigger point. Causes the ChxxHHAlarm to trigger when
the input signal moves above the configured trigger point. In terms of
engineering units.
REAL
The Rate alarm trigger point. Causes the ChxxRateAlarm to trigger when the
input signal changes at a rate faster than the configured rate alarm.
Configured in Engineering Units per second.
REAL
Allows a process alarm to remain set, despite the alarm condition
disappearing, as long as the input data remains within the deadband of the
process alarm.
The deadband value is subtracted from the High and High High Alarm Limits
to calculate the deadband thresholds for these alarms. The deadband value
is added to the Low and Low Low Alarm Limits to calculate the deadband
thresholds for these alarms.
Table 31
describes the 5069-IF8 module input tags.
Size
Definition
BOOL
Channel's operating state
BOOL
Indicates if a connection is running.
The module sets this tag to 0 when connected. If the module is not
connected, it changes the tag to 1.
BOOL
Indicates if any diagnostics are active or if the prognostics threshold is
reached.
SINT
Increments for each time a distinct diagnostic condition is detected, and
when a distinct diagnostic condition transitions from detected to not
detected.
Set to zero by product reset or power cycle. Wraps from 255 (-1) to 1
skipping zero.
BOOL
Indicates that channel data is inaccurate and cannot be trusted for use in
the application.
If the tag is set to 1, you must troubleshoot the module to correct the cause
of the inaccuracy.
IMPORTANT: Once the condition that causes the tag to change to 1 is
removed, the tag automatically resets to 0.
Rockwell Automation Publication 5000-UM005B-EN-P - November 2015
Module Tag Definitions
Appendix B
Valid Values
100.0 = default
0 = Rate Alarm is not used
Any value greater than zero = Trigger point
Any non-negative value
0 = default
Valid Values
• 0 = Idle
• 1 = Run
• 0 = Connection running
• 1 = Connection not running
• 0 = No diagnostics active
• 1 = One or more diagnostics are
active or the prognostics
threshold is reached
-128...127
The value of 0 is skipped except
during module power-up.
• 0 = Good
• 1 = Bad, causing fault
The typical causes of uncertain
data are the following:
– Channel is disabled
– Open Wire (input modules)
or No Load (output
modules) condition
– Underrange/Overrange
condition
– Short Circuit condition
We recommend that you first
troubleshoot the module to see if
the typical causes exist.
137

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

5069-of45069-iy45069-of8

Table of Contents