Chapter 7
Calibrate the Module
Calibrate the Input Modules
112
You apply low and high signal references to the 5069 Compact I/O analog input
module to calibrate it. The references must match the input range the channel is
using.
Table 25
lists the input ranges and corresponding references used to calibrate
the modules.
Table 25 - 5069 Compact I/O Analog Input Module Calibration References
Input Type
Voltage (V)
Current (mA)
RTD (5069-IY4 only)
Thermocouple (5069-IY4 only)
Calibrate the 5069-IF8 Module
This example describes how to calibrate a channel on the 5069-IF8 module for
use with a Voltage (V) input type. Complete the following steps:
1. Connect the voltage calibrator to the channel being calibrated.
2. Go online with the project and make sure the controller is in
Program mode.
3. Confirm that the channel to be calibrated is configured for the correct
Input Range.
4. On the Calibration category in the Module Properties dialog box, click
Start Calibration.
Rockwell Automation Publication 5000-UM005B-EN-P - November 2015
Input Range
Low Calibration
Reference
-10...10V
0.0V
0...10V
0...5V
0.0V
0...20 mA
4.0 mA
4...20 mA
1...500
1
2...1000
4...2000
8...4000
-100...100 mV
0.0 mV
High Calibration
Reference
10.0V
5.0V
20.0 mA
487
100.0 mV