4. LIGHTING INSTRUCTIONS

A. Open the isolation valve in the main gas line and turn gas control knob on the combination gas
valve to the "ON" position.
B. Switch on electrical circuit by turning the thermostat to the highest temperature setting.
C. The heater should attempt ignition and remain lit within thirty seconds. Note that the correspond-
ing exhaust fan is operating properly.
D. If ignition does not occur, then cut off electrical power by turning the thermostat to off position.
If heater back-fires during operation, then it must be turned off immediately.
WARNING:
Indication of back-firing:
A. Loud ignition noise, then followed by dis-
tinct hissing sound.
B. Little or no visible burning on the ceramic
tile.
C. Combustion is taking place inside the burner
body.

5. SHUT DOWN INSTRUCTIONS

A. Turn off electrical circuit for temporary shutdown.
B. Turn off the electrical circuit and turn gas control knob to the "OFF" position for complete shut-down.

6. AIR BORNE PARTICLES

Under certain conditions, heater may discolour due to ambient air borne particle deposits on the outside sur-
face. These deposits in no way affect the operation of the heater nor the manufacturer's warranties.

7. SERVICING GUIDE

Servicing of heater is essential for continued efficient operation. Servicing should be carried out
annually by qualified service personnel.
Clean the ceramic tile with compressed air. Avoid directing the air stream at the gasketing mate-
rial located between the tile and heater body. The air pressure must be lower than 20 psi.
Cause & remedy of back-firing:
A. Improper gas pressure entering the venturi
tube = check pressure.
B. Breakage of a ceramic tile and or gasketing
= replace damaged part.
C. Faulty sealing of the ceramic tile to the
burner body, caused by breakdown of gas-
keting material = contact your Schwank dis-
tributor.
Page 5