CONDENSATE DRAIN PUMP FOR HIGHWATERTEMP. (HUMIDIFIER)
These pumps are designed to collect the hot water produced by
the humidifier drain cycles, as well as the condensate produced.
The pump body is made from Cycoloy, a heat-resistant material,
the pre-wired safety float is a low voltage switch used to stop the
drain cycle in the unlikely event where the pump malfunctions.
The pump is started by internal float switches.
Technical specifications:
Tank capacity: 4 litres
Recommended maximum head: 6 m
Maximum water flow-rate: 900 l/h with zero head
Rated power: 0.6 A, 230 VAC
Power cable (2 m long)
Safety switch: max 4 A
Power supply voltage 220/240 VAC
Current draw: 0.7 A
Power consumption: 175 W
Dimensions
Height: 205 mm
Width: 300 mm
Depth: 150 mm
Weight: 3.6 kg
Electrical connections
Brown: Line
Blue: Neutral
Green/yellow: Earth
2 x black: Safety switch
Installation notes:
This pump is designed to be installed only horizontally, resting the
base on a perfectly flat, horizontal surface or fastening it horizon-
tally to the wall through the holes provided on the frame.
The pump requires a drain hose with an inside diameter of 9 mm.
Make sure the hoses are not choked or twisted along the path
between the pump and the point of drainage.
Securely fasten the hoses with a clamp to the pump outlet fitting,
to prevent them from coming loose and consequently causing
water to be released at high pressure.
IMPORTANT:
The pre-wired safety switch must always be used.
ACCURATE AX - AW - AD - AT - AF
SAFETY SWITCH
PUMP
MOTOR
PUMP START
SWITCH
PUMP FRAME
Maintenance guide
At least once every 6 months, pour a bactericidal solution into
the tank, to prevent accumulation of residues and sludge at the
bottom that may cause the pump to malfunction.
NB: Users must check that any chemicals contained in the con-
densate are compatible with operation of the pump.
IMPORTANT: Test pump operation by filling it with water until
the motor starts, to check for any leaks and verify correct
drainage of the water.
1400
1200
1000
800
600
400
200
0
1
2
3
4
HEAD IN METRES
BLACK
BLACK
LINE
NEUTRAL
EARTH
5
6
7
8
9
10
EN
63