OPERATING LIMITS

All versions. The AX - AW - AF - AD - AT units are designed for
operation within the following operating ranges (the limits are
considered for new units that have been correctly installed and
maintained):
Environmental conditions
from 20,0°C,45% RH at 32°C,55% RH
Outside conditions
from +10.0°C to +46.0°C in BASIC version without condensing
control
from -20.0°C to +46.0°C in MODULATING version with con-
densing control
from -45.0°C to +46.0°C in the LT version (low temperature).
OPTIONAL BASE MOULDING (OVER UNITS)
The "OVER" units are designed for the connections to pass
through the base of the unit; nonetheless, if there is no raised
floor (units with intake from the rear or front), to simplify the
connection of the pipes and cables, a base moulding must
be used.
The base moulding, available as an accessory, is epoxy-polyester
powder painted, in the same colour as the external panels on the
air-conditioner, measures 200 mm in height and is fitted with an
inspection panel.
On the right- and left-hand sides of the base moulding are six
pre-cut sections for passing the cables and pipes;
The moulding must be fastened to the air-conditioner using the
M6 threaded inserts already arranged on the base.
For the OVER units with intake from the bottom, base mouldings
are available with a height of 450 mm.
In this case too, the air-conditioner must be screwed to the base
moulding during the positioning phase.
Models
05
07
A1 mm
600
C1 mm
485
22
EN
10
15
18
20
26
1000
980
485
770
For the correct operation of the air-conditioner, the conditions
shown in the following graph must be observed:
t
46°C
35°C
10°C
-20°C
-45°C
20°C/45%
A1
C1
A1
C1
29
39
30
40
50
1530
770
ACCURATE AX - AW - AD - AT - AF
OPERATING ZONE
BASIC version
MOD cersion
LT version (low temperature)
28°C
32°C/55% t
ROOM TEMPERATURE
200
air-conditioner base
unit moulding
450
55
60
70
80
2080
2630
770
770