POSITIONING THE AIR-CONDITIONER

The air-conditioner can rest directly on the floor, perfectly level,
with a maximum difference in height of 5 mm between the ends
of the base: incorrect levelling may cause the condensate to leak
from the collection pan.
WARNING: the air-conditioner must be installed indoors
and in non-aggressive environments. Apply an elastic gasket
around the perimeter of the base to prevent the transmis-
sion of noise and vibrations.
SUPPORT FRAME (optional accessory)
A support frame is recommended:
- to allow the air-conditioner to be installed before assembling
the raised floor;
- to totally dampen any mechanical vibrations;
- to assist the laying of pipes and cables.
The support frame is available as an accessory and is adjustable in
height, indicated in the figure by the distance X, between 200 and
600 mm. To prevent the transmission of noise and vibrations, an
elastic gasket, at least 5 mm thick, should be inserted between the
panels of the raised floor and the frame, which must also be insu-
lated from the metallic structure of the floor.
NOTE: the frame must be fitted by the installer following the
instructions shown inside the packaging.
LOUVER KIT (optional accessory)
The louver is recommended to be used on UNDER units to devi-
ate the air flow and allow better distribution.
Models
05
07
L1 mm
600
P1 mm
485
OPERATING SPACE
Access is from the front only for all models.
This feature ensures easy access to all the main components in
the unit for installation and periodical maintenance.
Thanks to this feature, the units can be installed next to one
another, or alternatively fitted in racks.
To ensure easy maintenance, a space of at least 600 mm must be
left in front of the air-conditioner, as shown in the figure.
Make sure that the air intake and outlet are never
blocked, even partially.
Models
05
07
D mm
E mm
L mm
ACCURATE AX - AW - AD - AT - AF
10
15
18
20
26
1000
980
485
770
10
15
18
20
26
L1
X = 200 ÷ 600 mm
Raised floor
Elastic gasket
29
39
30
40
50
1530
770
L
29
39
30
40
50
>600
0
0
P1
X
ACCURATE
unit
Elastic gasket
55
60
70
80
90
2080
2630
770
770
E
D
55
60
70
80
90
EN
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Accurate adAccurate afAccurate atAccurate aw

Table of Contents