CALIBRATING THE CONTROL AND SAFETY DEVICES

After starting the air-conditioner, make the following adjustments:
- Room temperature (cooling and heating set point).
- Relative humidity (set point for humidification and dehumidifi-
cation);
- Dirty filter differential pressure switch: see the paragraph on
"CALIBRATING THE DIRTY FILTER SENSOR".
Symbol
Description
F1
High pressure switch
F2
Low pressure switch
Safety thermostat (versions T and H)
TH1
Safety valve
VS
52
EN
The calibration values of the control and safety devices must not
be altered.
Models
Activation
5
37,4 bar (opening)
7
10
15
18
38,7 bar (opening)
20
30
40
26
29
39
50
55
40,5 bar (opening)
60
70
80
90
All
3,0 bar (opening)
All
320 °C (opening)
05
41,5 bar
07
10
15
18
43 bar
20
30
40
26
29
39
50
55
45 bar
60
70
80
90
Differential
-
Manual reset
0,9 bar
3,9 bar (automatic)
-
Manual reset
-
ACCURATE AX - AW - AD - AT - AF
Reset
-