SOUNDPROOF SUCTION OR OUTLET PLENUM
The figure shows the soundproof plenum to be installed on the
top of the unit.
Models
05
07
L mm
600
P mm
500
H mm
DIRECT FREE COOLING PLENUM (UNDER UNITS)
This accessory is installed on the top of the unit, and is used to
take in cool outside air and then deliver it directly into the air-
conditioned environment. The plenum is supplied with 2
motorised dampers (one for the outside air + 1 for the inside
air), managed by the unit's microprocessor controlled, which
modulate the quantity of air taken in from the outside to ensure
the room temperature set point is maintained.
This accessory is not available on AF units.
P
SECTION A-A
Models
05
07
L mm
600
P mm
500
H mm
ACCURATE AX - AW - AD - AT - AF
10
15
18
20
1000
1000
500
790
350
10
15
18
20
1000
1000
500
790
600
P
26
29
39
30
40
1550
790
WARNING:
For correct installation, an elastic gasket should be fitted between
the plenum and the unit.
A PRESSURE-RELIEF DAMPER (supplied with the "FC CONNEC-
TION KIT") MUST BE USED, SO THAT THE AIR CAN DE DIS-
CHARGED DURING TOTAL FREE COOLING OPERATION.
L
FRONT VIEW
TOP VIEW
26
29
39
30
40
1550
790
L
50
55
60
70
2100
790
500
A
A
50
55
60
70
2100
790
840
H
80
90
2650
790
80
90
2650
790
EN
25