Manual 37223A
Wiring Single and Two-Pole Senders Simultaneously
An accuracy of ≤ 2.5% may be achieved when using single-pole senders. It is possible to combine single- and
two-pole senders. The specified accuracy of
tial voltage between the genset chassis ground and PE does not exceed +/- 2.5V.
Page 42/54
2.5% for single-pole sensors can only be achieved if the differen-
≤
Wiring diagram for combining single- and two-pole sensors
0/4 to 20 mA
[AI 03]
Resistive / VDO
0/4 to 20 mA
[AI 02]
Engine ground
Resistive / VDO
[AI 01]
0/4 to 20 mA
Resistive / VDO
Figure 5-35: Analog inputs (FlexIn) - wiring single- and two-pole senders
Terminal
Description
9
Analog input [AI 01] ground, connected with PE / engine ground
10
Analog input [AI 01]
11
Analog input [AI 02] ground, connected with PE / engine ground
12
Analog input [AI 02]
13
Analog input [AI 03] ground, connected with PE / engine ground
14
Analog input [AI 03]
Table 5-30: Analog inputs (FlexIn) - terminal assignment - wiring single- and two-pole senders
easYgen-3000 Series - Genset Control
PE
Protective Earth
+
Analog input [AI 03]
-
+
Analog input
Analog input [AI 02]
-
+
Analog input [AI 01]
-
Engine ground
It is not necessary to connect
the 0/4 to 20 mA sensors with
PE in case of two-pole sensors.
© Woodward
A
max
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²