Samson 3730-1 Mounting And Operating Instructions page 56

Series 3730 electropneumatic positioner
Table of Contents

Advertisement

Code list
Display, values
Code
[default setting]
Note: Codes marked by an asterisk (*) indicate that the positioner needs to be re-initialized afterwards
P13
Limit A2
0 to 100 % [98 %]
P14
Info w
Not initialized Displays external set point in 0 to 100 % according to the 4-20 mA
P15
Start initialization
P16
Start zero calibration
P17
Manual mode
P18
Reset
P19
Unassigned
P20
Firmware version
P21
Control mode
[PD]/PID
56
Software limit value A2 is displayed or can be changed in relation
to the operating range (steps of 0.5 %).
Initialized Indicates the internally adjusted set point in the positioner (adjust-
ed set point in 0 to 100 % according to the settings in P6 and P7).
Press
to display external set point (applied set point in 0 to
100 % according to the 4-20 mA signal).
signal.
Press
to cancel the initialization process. As a result, the valve
moves to the fail-safe position.
After a power supply failure during initialization, the positioner
starts with the values of the last initialization (if available).
The zero calibration process can be interrupted by pressing
The control valve returns to closed-loop operation.
Note: A zero calibration cannot be started when E1 error code ex-
ists.
After a power supply failure during zero calibration, the positioner
starts with the settings from the last zero calibration.
Turn
to enter the set point.
Parameters are reset to their default setting.
The positioner can only return to closed-loop operation after it has
been re-initialized.
Installed firmware version is displayed. Press
four digits of the serial number.
Allows an integral-action component to be included in the control
parameters
Description
to display the last
.
EB 8384-1 EN