Samson 3730-1 Mounting And Operating Instructions page 49

Series 3730 electropneumatic positioner
Table of Contents

Advertisement

Parameter codes
Codes marked by an asterisk (*) indicate that the positioner needs to be re-initialized afterwards
[...] Default settings
P0
Status indication
P1
Reading direction
P2*
Fail-safe position [ATO]/ATO
P3*
Pin position [35]
P4*
Nominal range [MAX]
P5
Characteristic [0]
P6
Set point [4 to 20 mA]
P7
w/x direction of action [>>]
P8*
Gain K
[50]
P
P9
Pressure limit 2.4 bar [OFF]
P10
End position w < [ON]
EB 8384-1 EN
P11
End position w > [OFF]
Limit value A1 switching threshold
P12
[2 %]
Limit value A2 switching threshold
P13
[98 %]
P14
Reading of set point w
P15
Start initialization
Start zero calibration
P16
P17
Start manual mode
P18
Load default settings
P19
Unassigned
P20
Firmware version
P21
Control mode [PD]/PID
Start-up