Hazardous Locations Certifications; North American Certifications - Emerson 3051 Quick Installation Manual

Pressure transmitter with hart protocol
Hide thumbs Also See for 3051:
Table of Contents

Advertisement

Quick Installation Guide
00825-0100-4001, Rev BA
November 2002

Hazardous Locations Certifications

North American Certifications

Factory Mutual (FM)
E5 Explosion-Proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition-Proof for Class II, Division 1, Groups E, F, and G.
Dust-Ignition-Proof for Class III, Division 1.
T5 (Ta = 85 °C), Factory Sealed, Enclosure Type 4x
I5 Intrinsically Safe for use in Class I, Division 1, Groups A, B, C, and
D; Class II, Division 1, Groups E, F, and G; Class III, Division 1
when connected per Rosemount drawing 03031-1019 and
00268-0031 (When used with a HART communicator);
Non-incendive for Class I, Division 2, Groups A, B, C, and D.
Temperature Code:T4 (Ta = 40 °C), T3 (Ta = 85 °C),
Enclosure Type 4x
For input parameters see control drawing 03031-1019.
Canadian Standards Association (CSA)
E6 Explosion-Proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition-Proof for Class II and Class III, Division 1, Groups E,
F, and G. Suitable for Class I, Division 2 Groups A, B, C, and D for
indoor and outdoor hazardous locations. Enclosure type 4X,
factory sealed
C6 Explosion-Proof and intrinsically safe approval. Intrinsically safe
for Class I, Division 1, Groups A, B, C, and D when connected in
accordance with Rosemount drawings 03031-1024. Temperature
Code T3C.
Explosion-Proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition-Proof for Class II and Class III, Division 1, Groups E,
F, and G. Suitable for Class I, Division 2 Groups A, B, C, and D
hazardous locations. Enclosure type 4X, factory sealed
For input parameters see control drawing 03031-1024.
Model 3051

Hide quick links:

Advertisement

Table of Contents
loading