BACnet Input Port Objects
Refer to the following two tables to configure the PowerScout24 input ports.
BACnet
Identifier
Configures the pulse input for I/O
13040
port 1
I/O port 1 pulse input
13050
accumulator
13060
I/O port 1 pulse input scaling
BACnet
Identifier
Configures the pulse input for I/O
13070
port 2
I/O port 2 pulse input
13080
accumulator LSW
13090
I/O port 2 pulse input scaling
Shop for Dent products online at:
Object Name
0 = off, pulse input disabled
1 = rising edge, pulse counter increments, falling edges are ignored.
If pulse output is enabled, it is disabled when this configuration is
set.
2 = falling edge, pulse counter increments, rising edges are ignored.
If pulse output is enabled, it is disabled when this configuration is
set.
3 = both edges pulse counter increments. If pulse output is enabled,
it is disabled when this configuration is set. (Note when pulse is off,
I/O control is enabled)
Setting this register to a value other than 0, forces register 45110 to
0.
Scaled pulse
x1000 decimal fraction of scale factor
Table F-8: BACnet Port 1 Pulse Input
Object Name
0 = off, pulse input disabled
1 = rising edge, pulse counter increments, falling edges are ignored.
If pulse output is enabled, it is disabled when this configuration is
set.
2 = falling edge, pulse counter increments, rising edges are irnored.
If pulse output is enabled, it is disabled when this configuration is
set.
3 = both edges pulse counter increments. If pulse output is enabled,
it is disabled when this configuration is set. (Note when pulse is off,
I/O control is enabled)
Setting this register to a value other than 0, forces register 45210 to
0.
Scaled pulse
x1000 decimal fraction of scale factor
Table F-9: BACnet Port 2 Pulse Input