Dent PowerScout 3 Plus Operator's Manual page 87

Power meters
Table of Contents

Advertisement

Object
Identifier
12011
CT1 Value
12012
CT2 Value
12013
CT3 Value
12030
CT Pulse Scalar
12040
Demand Window
12050
Volts Multiplier
12061
CT1 Amps Multiplier
12062
CT2 Amps Multiplier
12063
CT3 Amps Multiplier
12070
Com Settings
12080
Service Type
12090
Line Frequency
12130
CT Type All
(PS3 Only)
12131
CT1 Type
12132
CT2 Type
12133
CT3 Type
Shop for Dent products online at:
Name
CT1 Value
CT2 Value
CT3 Value
Changes the scaling of the output pulses
Demand window size in minutes; default is 15 min
Multiply volts values by this scalar. For use with stepdown
transformer. Affects all parameters that use volts.
Multiply CT1 amps values by this scalar. For use with stepdown
transformer. Affects all parameters that use amps.
Multiply CT2 amps values by this scalar. For use with stepdown
transformer. Affects all parameters that use amps.
Multiply CT3 amps values by this scalar. For use with stepdown
transformer. Affects all parameters that use amps.
Baud: 900=9600, 1900=19200, 3800=38400, 5700=57600,
7600=76800, 11500=115200
Parity: Add 00 = NO, Add 10 = ODD, Add 20 = EVEN
Stop bit: Add 0 = 1 (UART does not permit 0 stop bits), Add 1 = 1, Add
2 = 2
E.g., 901 = 9600 baud, no parity, 1 stop bit
A value of 1 configures the meter for Delta.
A value of 0 configures the meter for Wye.
A value of 2 configures the meter for Single Phase (PS24 only).
Line frequency setting for metering. 50 = 50 Hz, 60 = 60 Hz
Writes same type for all CTs: 1=MilliVolt, 2=Rogowski
1=MilliVolt, 2=Rogowski
1=MilliVolt, 2=Rogowski
1=MilliVolt, 2=Rogowski
87