Object
Identifier
9150
Apparent PF L1
9180
Apparent PF L2
9210
Apparent PF L3
10000
Measured Line Frequency
10010
Time Since Reset
P
P
OSITIVE
OWER
Object
Identifier
1080
kW System Average Positive
1110
kW System Maximum Positive
1140
kW System Minimum Positive
2010
kWh System Total Positive
2040
kWh L1 Positive
2070
kWh L2 Positive
2100
kWh L3 Positive
6010
kVARh System
6020
kVARh System Total Positive
6050
kVARh L1 Positive
6080
kVARh L2 Positive
6110
kVARh L3 Positive
7001
kVAh System Total Positive
7020
kVAh L1 Positive
7050
kVAh L2 Positive
7080
kVAh L3 Positive
Shop for Dent products online at:
Name
/E
M
NERGY
EASUREMENT
Name
PowerMeterStore
www.
Description
* System=sum of three phases
Individual Phase apparent Power Factors (PF)
"
"
Line Frequency (Hz)
Seconds since accumulator registers were reset.
O
BJECTS
Description
* System=sum of three phases
Equals kWh System Positive / (Time Since Reset /3600 seconds/Hr)
(resettable) (Signed Net)
System Highest Instantaneous Positive Draw Since Reset (kW)
(Signed Net)
System Lowest Instantaneous Positive Draw Since Reset (kW,
resettable)
System True Energy (kWh) Positive (Signed Net)
Individual Phase True Energy (kWh) (Signed)
"
"
System Total Reactive Energy (Signed Net)
System True Energy (kVARh) Positive (Signed Net)
Individual Phase Reactive Energy (kVAR) (Signed)
"
"
System Total Positive Apparent Energy (kVAh) (Signed Net)
Accumulates only when kW is positive
Individual Phase Apparent Energy (kVAh) (Signed)
"
"