Positive Power/Energy Measurement Registers - Dent PowerScout 3 Plus Operator's Manual

Power meters
Table of Contents

Advertisement

P
P
OSITIVE
OWER
Modbus
46001
6000
46002
6001
46003
6002
46004
6003
46005
6004
46006
6005
46007
6006
46008
6007
46009
6008
46010
6009
46011
6010
46012
6011
46013
6012
46014
6013
Shop for Dent products online at:
/E
M
NERGY
EASUREMENT
Offset
Register
Positive kWh System LSW
Positive kWh System MSW
Positive kW System
kW Demand System Max
kW Demand System Now
Positive kW System Max
Positive kW System Min
Positive kVARh System LSW
Positive kVARh System MSW
Positive kVAR System
kVAh System LSW
kVAh System MSW
kVA System
Positive Displacement PF
System
PowerMeterStore
www.
R
EGISTERS
* System=sum of three phases
System Positive True Energy LSW (kWh, resettable)
System Positive True Energy MSW (kWh, resettable)
System Positive Instantaneous Positive True Power
(kW) (net sum of all individual kWs, if sum is negative
value=0)
System Maximum Demand (peak demand).
Average Power (kW) for most recent demand window
System Net Highest Instantaneous Positive Draw
Since Reset (kW, resettable)
System Net Lowest Instantaneous Positive Draw Since
Reset (kW, resettable)
System Net Positive Reactive Energy LSW (kVARh,
resettable)
System Net Positive Reactive Energy MSW (kVARh,
resettable)
System Net Instantaneous Positive Reactive Power
(kVAR) (net sum of all individual kVARs, if sum is
negative value=0)
System Apparent Energy, LSW (resettable)
System Apparent Energy, MSW (resettable)
System Instantaneous Apparent Power
System Positive Displacement Power Factor (dPF);
Register is 100x actual value (If the System dPF
(44014) is positive, this register will contain that value
else it will be zero)
73
Description
1.877.766.5412
.com