Dent PowerScout 3 Plus Operator's Manual page 96

Power meters
Table of Contents

Advertisement

BACnet Output Port Objects
Refer to the following two tables to configure the PowerScout output ports when using the BACnet
protocol. Remember to add the correct increment of 20000 to the base object number that designates
each element on the PS24. See Addressing an Element.
PS 3
Object
Object
Identifier
Identifier
13020
13100
13110
PS3
Object
Identifier
Port 2 output control when used
13030
as an on/off—open/closed switch
Digital Port 2 Configuration
13150
Turns pulses on/off
13160
Port 2 pulse output relay type
Shop for Dent products online at:
PS24
Port 1 output control when used as an
NA
on/off—open/closed switch
Digital Port 1 Configuration
15000
Turns pulses on/off
15010
Port 1 pulse output relay type
Table F-4: BACnet Digital Port 1 Pulse Output
Name
Table F-5: PS3 BACnet Digital Port 2 Pulse Output
PowerMeterStore
www.
Name
0 = output LOW (closed) 1 = output HIGH
(open) [default]
Object 13100 present value must = 0 to use
0 = No pulses, Port may be used as an
on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
0 = normally open (HIGH)
1 = normally closed (LOW)
Detailed Description
0 = output LOW (closed)
1 = output HIGH (open) [default]
Object 13150 present value must = 0 to use
0 = No pulses, Port may be used as an on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
0 = normally open (HIGH)
1 = normally closed (LOW)
96
Detailed Description
1.877.766.5412
.com

Advertisement

Table of Contents
loading

Related Products for Dent PowerScout 3 Plus

This manual is also suitable for:

Powerscout 24

Table of Contents