Dent PowerScout 3 Plus Operator's Manual page 72

Power meters
Table of Contents

Advertisement

Modbus
44057
4056
44058
4057
44059
4058
44060
4059
44061
4060
44062
4061
44063
4062
44064
4063
44080
4079
44081
4080
44082
4081
44083
4082
44084
4083
Shop for Dent products online at:
Offset
Register
Amps L2
Amps L3
Volts L1 to Neutral
Volts L2 to Neutral
Volts L3 to Neutral
Time Since Reset LSW
Time Since Reset MSW
Data Tick Counter
kW System Average
kW Demand System Min
kVA Demand System Max
kVA Demand System Now
kVAR Demand System Max
PowerMeterStore
www.
Description
* System=sum of three phases
"
"
Individual Phase to Neutral Voltages (V)
"
"
Seconds since KWH register was reset. LSW
Seconds since KWH register was reset. MSW
Internal sample count (gets cleared every minute):
may be used to determine if sample read is a newer
sample than last read.
Equals KWH_SYSTEM_L&M ÷ (TimeSinceReset_L&M
seconds /3600 seconds/Hr) (resettable)
System Minimum Demand (kW)
System Maximum Instantaneous kVA Demand (kVA,
resettable). It displays the default value after a CAM
until 1 demand window elapses. After a power cycle or
CPU reset the value is not reset but it does not update
again until 1 demand window elapses.
System Average kVA Demand For the most recent
(current) Demand Window.(resettable) Displays the
default value after a CAM or reset, or power cycle.
Updates every min thereafter. True demand value
takes a demand period to get to actual value. Similar
to 44005
System Maximum kVAR Demand (kVAR, resettable). It
displays the default value after a CAM until 1 demand
window elapses. After a power cycle or CPU reset the
value is not reset but it does not update again until 1
demand window elapses.
72