Additional Charge - Daikin FHC20JEVLK Installation Manual

R22 split series
Table of Contents

Advertisement

The refrigerant is pre-charge in the outdoor unit. If the piping length is less than 7.5m, then additional charge after
vacuuming is not necessary. If the piping length is more than 7.5m then use the additional charge value as indicated in the
table.
Additional refrigerant charge [g] per additional 1m length as tabulated (for R22 models)
Cooling only
Model
Additional charge [g/m]
Model
Additional charge [g/m]
Model
Additional charge [g/m]
Heat Pump Unit
Model
Additional charge [g/m]
Model
Additional charge [g/m]
Model
Additional charge [g/m]
Example:
FHC20JEVLK & RD20JEVLK with 13m piping length, additional piping length is 5.5m. Thus,
Additional charge = 5.5[m] x 22[g/m]
= 121[g]
* When connect with FHC25JEVLK and FHYC25JEVLK, additional 0.2kg refrigerant charge is needed for 3.0m to
7.5m piping length.

ADDITIONAL CHARGE

Indoor
Outdoor
Indoor
Outdoor
Indoor
Outdoor
Indoor
Outdoor
Indoor
Outdoor
Indoor
Outdoor
! CAUTION
1-19
FHC20JEVLK
RD20JEVLK
22
FHC30JEVLK
RD30JEVLK
57
FHC50JEVLK
RD50JETLK
58
FHYC20JEVLK
RYD20JEVLK
22
FHYC30JEVLK
RYD30JEVLK
57
FHYC50JEVLK
RYD50JETLK
58
FHC25JEVLK
RD25JEVLK*
55
FHC40JEVLK
RD40JEVLK
40
FHYC25JEVLK
RYD25JEVLK*
55
FHYC40JEVLK
RYD40JEVLK
40